✉ pe@qp.sgWhatsApp +65 9800 4385
PE Consultants Pte LtdFSC02 & Regulated Fire Safety Products

Fire-Rated Floor FSC02 Endorsement Singapore

CoC and DoC review and Appropriate QP verification of fire-rated floor systems — Table 11A item 5.

Direct answerA fire-rated floor is a complete tested system, not merely a fire-resistant board or ordinary flooring product. Under SCDF Fire Code 2023 Table 11A it requires a valid CoC and a DoC, and the Appropriate QP must verify that the installed floor — board, support, joints, fixings and penetrations — matches the certified system before endorsing FSC02.

Last reviewed: 24 September 2026 · Primary reference: SCDF Fire Code 2023, Chapter 11 and Table 11A · Prepared by PE Consultants Pte Ltd

Warning: “An ordinary fire test report, reaction-to-fire classification or manufacturer’s brochure is not automatically a valid SCDF CoC. The proposed product and complete assembly must be checked against the current SCDF certification requirements.”

Why a fire-rated floor is certified as a system

Fire resistance of a floor depends on how every component performs together: the floor board or deck, the supporting joists or beams, any insulation, the ceiling layers beneath, fixings, joints and service penetrations. The CoC therefore covers a defined configuration. A floor built with a different board thickness, joist spacing, span or fixing pattern may fall outside the CoC even if the same board brand is used.

Fire-rated floor tested as a complete system Cross-section of a fire-rated floor showing the floor board, supporting joists or steel beams, insulation, ceiling board layers, fixings, joints and a service penetration sealed with fire stopping. All components form one tested and certified system. Floor board / deck (brand, model, thickness, density per CoC) Supporting joists / steel beams Insulation (if tested) Ceiling board layers, joints and fixings as certified Penetration + fire stopping One tested system → one CoC scope → project DoC → QP verification → FSC02
Illustrative only. A fire-rated floor is certified as a complete tested assembly; changing any component can take the installation outside the CoC scope.

What the QP reviews for fire-rated floor FSC02

  • CoC number and issue number
  • Validity status
  • Manufacturer and CoC holder
  • Brand and model
  • Board or system composition
  • Thickness and density
  • Fire-resistance period
  • Loadbearing capacity
  • Integrity
  • Insulation
  • Test standard
  • System test report
  • Material test report
  • Installation configuration
  • Supporting structure
  • Joints, fixings and interfaces
  • Penetrations and fire stopping
  • Project-specific DoC
  • Site photographs and installation records

Penetrations through the floor must be sealed with certified products — see fire stopping FSC02. Where a fire-rated ceiling forms part of the floor’s protection, see fire-rated ceiling FSC02.

Fire-rated floor CoC and DoC

Fire-rated floor is listed in Table 11A as a product requiring a CoC and a DoC. The CoC is issued by an SAC-accredited Certification Body; the DoC is issued to the CoC holder for the certified products supplied. Our CoC and DoC review service checks both documents against each other and against the installed floor.

Examples of Fire-Rated Floor CoC Records Identified in the Certification Register

At the time of preparation, the following fire-rated floor CoC records were identified under Promat Building System Pte Ltd. They are shown as examples of how fire-rated floor systems are described in a Certification Body register — by CoC number, brand and system model.

CoC no.Brand / systemModel(s)CoC holder
21A0463PROMATECT-250P250.13.60, P250.13.12Promat Building System Pte Ltd
20A0271PROMATECT-L500PE.11.12 ENPromat Building System Pte Ltd
20A0256PROMATECT-SPS.13.60, PS.13.12Promat Building System Pte Ltd
20A0248DURASTEELDU.13.60, DU.13.12, DU.13.24Promat Building System Pte Ltd
18A0151PROMATECT-250 and KALSI systemAs stated in CoC appendixPromat Building System Pte Ltd
11A0050DURASTEELDU.13.24Promat Building System Pte Ltd

Certificate status, issue number, scope and validity should be verified directly with the relevant SAC-accredited Certification Body before submission or installation.

This list is not exhaustive and does not represent all valid fire-rated floor CoCs in Singapore. Other manufacturers and Certification Bodies hold fire-rated floor certifications. Inclusion is not an endorsement of any manufacturer, and PE Consultants is not affiliated with the CoC holder. Withdrawn, terminated or superseded certificates are not presented here as current.

Our FSC02 work process

  1. Submit product and project informationSend the project details, CoC, DoC and product literature to pe@qp.sg or through the enquiry form.
  2. Review the product category under SCDF Table 11AWe confirm the regulated product category, the current Table 11A reference and whether FSC02 applies.
  3. Check the CoC, test reports, system scope and validityCoC number, issue number, holder, model and scope are checked against the Certification Body’s directory.
Ready to start? Send your CoC and product details to pe@qp.sg
  1. Check the DoC, serial label or certified markWhere applicable, we confirm the representation of compliance matches the certified product and the project.
  2. Inspect or verify the installed productQP site inspection or verification of the installation against the certified system and approved fire safety design.
  3. Prepare the FSC02 endorsement and supporting documentsSubject to satisfactory review, we prepare the FSC02 endorsement and supporting submission documents.
Send your CoC and product details to pe@qp.sgRequest FSC02 Assessment

Frequently asked questions

Does a fire-rated floor require a CoC?

Yes. Fire-rated floor is a regulated product under SCDF Fire Code 2023 Table 11A (item 5). It must hold a valid Certificate of Conformity issued by an SAC-accredited Certification Body recognised by SCDF, and the CoC must cover the complete floor system as installed — not only the board.

Does a fire-rated floor require a DoC?

Yes. Table 11A identifies the fire-rated floor as a product for which a Declaration of Compliance is required. The DoC is issued by the Certification Body to the CoC holder and should correspond to the certified system and the project or batch supplied. The QP checks that the DoC matches the CoC and the installed floor.

Is a fire test report the same as a CoC?

No. A fire test report records how a specimen performed in one test. A CoC is issued by an SAC-accredited Certification Body after product testing, factory assessment and the applicable surveillance regime under the SCDF Product Listing Scheme. An ordinary fire test report, reaction-to-fire classification or manufacturer’s brochure is not automatically a valid SCDF CoC.

What documents are needed for fire-rated floor FSC02?

Typically: the current CoC and CoC appendix (number, issue number and validity), the project DoC, system and material test reports, shop drawings showing the tested configuration, supporting structure, joints, fixings and penetrations, method statement, delivery records, site photographs and installation records, and the project and Appropriate QP details. See fire-rated floor FSC02 endorsement.

Can a product be used if its CoC model differs from the installed model?

Generally no. The installed product must match the CoC exactly — brand, model, composition, thickness, density, configuration and manufacturer. A different model, revised build-up or alternative manufacturer needs its own CoC coverage, or a revised CoC issued by the Certification Body. The QP cannot extend a CoC’s scope by professional judgement. See CoC and DoC review.

Request FSC02 Assessment

Send your CoC, DoC, product details and installation information to PE Consultants Pte Ltd. FSC02 endorsement is subject to review of the product documentation, certification scope, installation details and the QP’s professional assessment.

Email: pe@qp.sg  |  WhatsApp: +65 9800 4385

Official sources

Last reviewed: 24 September 2026. Regulatory references are to the SCDF Code of Practice for Fire Precautions in Buildings 2023 (Fire Code 2023), Chapter 11 and Table 11A.

WhatsApp WhatsApp