Is a Fire Test Report the Same as a CoC?

Fire safety product installation certificate requirements start with the right certificate.

Direct answerNo. A fire test report records one specimen’s performance in one test. A Certificate of Conformity is issued by an SAC-accredited Certification Body after testing, factory assessment and ongoing surveillance under the SCDF Product Listing Scheme. An ordinary fire test report, reaction-to-fire classification or brochure is not automatically a valid SCDF CoC.

Last reviewed: 24 September 2026 · Primary reference: SCDF Fire Code 2023, Chapter 11 and Table 11A · Prepared by PE Consultants Pte Ltd

What each document proves

DocumentWhat it showsEnough for FSC02?
Fire resistance test reportPerformance of one tested specimenNo — supporting evidence only
Reaction-to-fire classificationSurface spread or combustibility classificationNo
Manufacturer’s brochure or overseas certificateMarketing or foreign-market complianceNo
SCDF-scheme CoC from a recognised Certification BodyCertified product and scope under Table 11ARequired, together with DoC or label where applicable and QP verification

For a worked example, see fire-rated floor CoC and DoC.

Frequently asked questions

Is a fire test report the same as a CoC?

No. A fire test report records how a specimen performed in one test. A CoC is issued by an SAC-accredited Certification Body after product testing, factory assessment and the applicable surveillance regime under the SCDF Product Listing Scheme. An ordinary fire test report, reaction-to-fire classification or manufacturer’s brochure is not automatically a valid SCDF CoC.

Is “SCDF-approved product” the correct term?

Usually not. SCDF does not approve or endorse individual CoCs. The accurate description is a regulated fire safety product certified by an SAC-accredited Certification Body under the SCDF Product Listing Scheme, holding a valid CoC. The phrase “SCDF-approved” is often misleading and should not be relied on without checking the CoC.

Can a product be used if its CoC model differs from the installed model?

Generally no. The installed product must match the CoC exactly — brand, model, composition, thickness, density, configuration and manufacturer. A different model, revised build-up or alternative manufacturer needs its own CoC coverage, or a revised CoC issued by the Certification Body. The QP cannot extend a CoC’s scope by professional judgement. See CoC and DoC review.

Request FSC02 Assessment